The Inspection Explained

Landlord Electrical Safety Certificate: What Is Checked (and What Is Not)

A landlord electrical safety certificate checks the fixed electrical installation of the property: the consumer unit, the protective devices, the earthing and bonding, the wiring of every circuit and the fixed accessories and equipment. It does not test appliances. The inspection produces an Electrical Installation Condition Report with a satisfactory or unsatisfactory result, a schedule of test results and any observations coded by seriousness. We provide landlord electrical safety certificates across Greater London, carried out by NICEIC registered electricians.

Have your postcode, the number of bedrooms and consumer units, and your current report's next-inspection date ready.

  • NICEIC Approved Contractor since 2021
  • Price confirmed before we attend
  • Phone line open 24/7

What Is Inspected and Tested

The inspector works through the installation from the supply inwards, looking first and then testing with instruments. Five areas make up the report, and each one below is what you are paying for when you book a landlord electrical safety certificate.

01

Consumer unit and protective devices

The consumer unit is opened and inspected for condition, correct labelling of each circuit, secure connections, signs of overheating and the right protective devices. The inspector checks that RCDs are present where BS 7671 requires them, that breakers or fuses are correctly rated for their circuits and that the enclosure itself is sound.

02

Earthing and main protective bonding

The earthing arrangement is identified and tested so that a fault will disconnect the supply quickly. Main protective bonding conductors to the incoming gas and water pipework, and to any other extraneous metalwork, are checked for presence, size and connection. Missing or undersized bonding is one of the most common observations on any report.

03

The wiring and each circuit

Every circuit is tested with instruments and the readings are recorded on the schedule of test results. In plain words: insulation resistance checks that the cable insulation is not breaking down; continuity checks that the protective conductor runs unbroken to every point; earth fault loop impedance checks that a fault would trip the device quickly; and RCD operation checks that each RCD trips as fast as it should.

04

Sockets, switches and fittings

A sample of accessories in each room is inspected: sockets, switches, light fittings, pendants and fused spur units. The inspector looks for cracked or broken fronts, loose fixings, scorching or discolouration that suggests heat, exposed conductors, and accessories in bathrooms or outdoors that are not suitable for the location.

05

Fixed equipment

Equipment wired directly into the installation is included: electric showers, cookers and hobs on their own circuits, immersion heaters, storage heaters, extractor fans and outside lighting. The inspector checks the circuit serving each item, its protective device, its isolation switch and the condition of the connection, but does not test the appliance's own internal workings.

Sampling, Limitations and the Schedule of Items

The extent of the inspection and any limitations are agreed before it begins and recorded on the front of the report, so that anyone reading it knows exactly what was and was not covered. A limitation might be a locked room, a loft with no safe access, a tenant's furniture built in against a socket, or a circuit that could not be switched off because it served medical equipment. Where a full inspection of every accessory is not practicable, the inspector samples a proportion in each area and increases the sample if faults appear. The report then contains two schedules: the schedule of inspections, which lists each item examined with a tick, a cross or a note, and the schedule of test results, which records the instrument readings for every circuit. Read the limitations before you read the result.

What the Codes Mean for You

Observations on the report carry one of four codes. C1 means danger is present: the inspector will make it safe on the spot where possible, or isolate it, and tell you immediately. If you ever notice sparking, burning smells or a shock from an installation, switch off at the consumer unit if it is safe to do so and call a qualified electrician; in an emergency call 999. C2 means potentially dangerous and FI means further investigation is required; either makes the report unsatisfactory and starts your 28-day duty. C3 means improvement recommended and does not on its own make the report unsatisfactory. The inspector decides each code on site from what is found, so no feature of a property automatically earns a particular code. Unsatisfactory EICR: the landlord's 28-day duty explains what happens next.

What Is Not Checked

The EICR does not cover anything that plugs in. The tenant's own appliances are theirs and are never part of the report. The appliances you supply with the tenancy, such as the fridge, the washing machine, the kettle or portable heaters, are not tested either; they are covered by PAT testing for landlords, which we can carry out on the same visit so that both records carry the same date. The gas installation is a separate duty under separate rules and is not part of the electrical inspection, although the inspector does check that the gas pipework is bonded. Smoke and heat alarms are noted on the report where they are wired into the installation, but the EICR does not certify them; test them and record the result yourself.

Preparing Your Tenants for the Visit

Tell your tenants what to expect, and the visit will go more smoothly for everyone.

1

Give notice

Give the tenants reasonable written notice of the date and time, normally at least 24 hours, and explain that the inspection is a legal requirement that protects them.

2

Arrange access to every room and the consumer unit

The inspector needs to reach every room, the consumer unit, the meter and, where possible, the loft. Ask tenants to clear anything stored against the unit and to leave cupboards with sockets in them accessible.

3

Warn that the power goes off in stages

Each circuit is switched off in turn for testing, so computers should be saved and shut down and anyone working from home should plan around it. Fridges and freezers are fine for the length of the visit.

4

Expect the report by email afterwards

The report arrives as a PDF by email. Give a copy to the tenants and note the next-inspection date it states; how often a landlord needs an EICR explains what that date means for you.

Related Guides

01

Certificate Cost

What a landlord electrical safety certificate (EICR) costs in London: typical prices by property size, what moves the price, and what is quoted separately.

Read the guide
02

The 2020 Regulations

A plain guide to the Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020: who they cover, the five-year duty and penalties.

Read the guide
03

How Often an EICR

How often a landlord needs an EICR: the five-year maximum, the inspector's next-inspection date, what a new tenancy changes, and how an EIC counts.

Read the guide

Landlord electrical safety certificates

Book Your Inspection

Call All Service 4 U on 020 3740 6785 with the address and the number of bedrooms and we will confirm a fixed price before we attend. Our NICEIC registered electricians inspect and test the whole fixed installation, explain any observations in plain words and send the report as a PDF by email. Phone line open 24 hours a day, seven days a week, with evening and weekend appointments available. Contact us to book.

020 3740 6785

Frequently Asked Questions

How long does the inspection take?

It depends on the size of the installation: the number of circuits, the number of consumer units, how many accessories there are to sample and how easy access is. A one-bedroom flat with a single consumer unit is a shorter visit than a four-storey HMO with two boards and a loft conversion. We will give you a realistic idea when you book, once we know the property.

Does the power go off?

Yes, in stages. Some tests can only be carried out with a circuit isolated, so each circuit is switched off in turn and then restored. The whole property is rarely off at once, and never for the whole visit. Tenants should save work on computers before the inspector arrives; fridges and freezers are not affected by a short interruption to their circuit.

Does it include the appliances?

No. The EICR covers the fixed installation up to and including the socket, the switch or the connection unit. Anything that plugs in, whether yours or the tenant's, is outside it. Appliances you supply can be PAT tested on the same visit as a separate record, and fixed items such as showers and cookers are covered as part of their circuit, not as appliances.

Is a visual inspection enough?

No. A visual-only check can be useful between full inspections, but the 2020 Regulations require the installation to be inspected and tested, and the schedule of test results is the part of the report that councils and tenants rely on. Without instrument readings for insulation resistance, continuity, loop impedance and RCD operation, the report cannot say whether the installation is safe.

Do I need to be there?

No. Most landlord inspections are arranged with the tenant or the letting agent providing access, and the report is sent to you by email afterwards. If you want to walk the property with the electrician, you are welcome to, and it can help if you have questions about the installation. Either way, someone needs to be there to let the electrician in.

Still have a question or need urgent assistance? Call 020 3740 6785, tell us what has happened and we will tell you what happens next.

Call 020 3740 6785 · 24/7